Chapter 10 Auto-tuning Process | IED-S

10-6 Tuning in Manual Mode

10-6-1 Leveling Plate Length
Elevator Rated Speed
10-6-2 Installation Position of Door Zone Leveling Sensors
Installation positions of DZU (Upper Leveling Sensor), DZD (Lower Leveling Sensor), and SX1
(Door Zone Sensor).
1. When the elevator is leveling, DZU, SX1, and DZD are all activated.
DZU is about 10–20 mm at the upper edge of the leveling plate.
SX1 is in the middle of the leveling plate.
DZD is about 10–20 mm at the lower edge of the leveling plate.
2. When the elevator is at the top floor and levels upward before reaching upper limit switch
(LSU), DZU leaves the leveling plate but DZD does not.
3. When the elevator is at the bottom floor and levels downward before reaching lower limit
switch (LSD), DZD leaves the leveling plate but DZU does not.
< 1 m/s
1
2 m/s
2
3 m/s
3
4 m/s
4
5 m/s
> 5 m/s
Leveling Plate Length
> 150 mm
> 200 mm
> 300 mm
> 400 mm
> 500 mm
> 600 mm
10-18