Chapter 12 Descriptions of Parameter Settings

03 Function Settings

Hoistway Auto-tuning
Settings 0–1
 When using the hoistway auto-tuning function, you must set IED-S to the inspection mode first
(manually) and set Pr.03-00=1. Then, change the elevator to automatic control, and the hoistway
auto-tuning function is enabled. The elevator runs downward to the lower limit first, and then runs
upward and searches the leveling signals and forced deceleration switch signals for each floor
for adjustment, and stops until it reaches the upper limit. Finally, it runs to the highest floor to stop.
Then, the hoistway auto-tuning is finished.
 During hoistway auto-tuning, the displayed value for Pr.03-00 is 1. It automatically clears to 0
until the auto-tuning process is finished.
 NOTE: If you stop the auto-tuning process by setting Pr.03-00 to 0, the auto-tuning process stops
but the elevator cannot run normally. You must finish the tuning process once it starts.
 Sets the running speed during hoistway tuning (Pr.04-03 Hoistway Auto-tuning Speed). The
slower the speed, the accurate the tuning. The suggested speed is 0.25 m/s.
 If the fault code F141 occurs during the hoistway auto-tuning, increase the setting time for
Pr.03-24. After the hoistway turning is finished, change Pr.03-24 to normal settings values.
Highest Physical Floor
Lowest Physical Floor
Settings 1–64F
 If the actual floor is from B1F to 10F, then the lowest physical floor is 1; the highest physical floor
is 11.
 When using group controls, set the physical floor based on the highest and lowest physical floors.
Example:
If the actual floor for Elevator 1 is B1F–9F,
If the actual floor for Elevator 2 is 1F–10F,
Elevator/Physical Floor
Single
Control
Elevator/Physical Floor
Group
Control
Group Control Station Number
Settings 0–7
 You can only use one group control station number at one time among all group control
elevators.
Group Control Enabled
Settings 0–1
Lowest Physical Floor
Elevator 1
Elevator 2
Lowest Physical Floor
Elevator 1
Elevator 2
0: Single control operation
1: Group control operation
12-03-1
Chapter 12 Descriptions of Parameter Settings | IED-S
: You can set this parameter during operation.
Highest Physical Floor
1
1
Highest Physical Floor
1
2
Default: 0
Default: 1
10
10
10
11
Default: 0
Default: 0