Chapter 12 Descriptions of Parameter Settings | IED-S
Floor Position Display for Car/Hall Call
Settings
Elevator Lock Main Landing
Settings
 Sets the physical floor that the elevator automatically returns after the elevator lock is activated.
Note that once the elevator lock is activated, the elevator does not respond to any car/hall calls.
Primary Main Landing at Fire Emergency
Settings
 Sets the physical floor that the elevator automatically returns when fire emergency function is
enabled or fire emergency multi-function terminals are activated.
Secondary Main Landing at Fire Emergency
Settings
 Valid only for fireman. Press door open/close buttons continuously to open and close the door.
ICB (Car Command Board) Mode
Settings
 The installation method for car command boards:
0–1
0: Displays floor using Pr.00-35 (Nearest Stop Floor)
1: Displays floor using Pr.00-17 (Current Floor) (current floor position)
0–164S
0: Elevator lock is disabled
1–64: Front door
101–164: Rear door
0–164S
0: Primary fire emergency is disabled
1–64: Front door
101–164: Rear door
0–164S
0: Secondary fire emergency is disabled
1–64: Front door
101–164: Rear door
0–3
0: Single door mode
1: Single door disability mode
2: Front and rear door mode
3: Front and rear door disability mode
Cartop Board
EA-CT01
J5
1
2
12-03-10
J4
3
Car
Command
Board
EA-CP16
4
Default: 0
Default: 1
Default: 1
Default: 1
Default: 0