Frame D
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, +1,
Model
Max.
Wire
Gauge
IED150S23A
IED185S23A
36 mm²
IED220S23A
[2 AWG]
IED220S43A
IED300S43A
NOTE
1. Select copper wires with rated voltage of 600 V and
temperature resistance of 75°C or 90°C for wiring.
2. For IED220S23A, use copper wires with rated voltage of
600 V and temperature resistance of 90°C or above.
3. For UL installation compliance, use copper wires when
installing. The wire gauge is based on a temperature
resistance of 75 °C, in accordance with UL requirements
and recommendations. Do not reduce the wire gauge when
using high-temperature resistant wires.
4. Use specified ring lug for terminal wiring. See Figure 1 and
Figure 2 for ring lug specifications. For other types of
wiring, use the wires that comply with local regulations.
5. After crimping the wire to the ring lug (must be UL and CSA
approved R/C (YDPU2)), then install heat shrink tubing
rated at a minimum of 600 V
(see Figure 2).
Frame D
Main circuit terminals:
+2/B1, -, B2
Min.
Screw Size
Wire
and Tightening
Gauge
Torque (±10%)
25 mm² [4 AWG]
36 mm² [2 AWG]
50 kg-cm
(43.4 lb-in.)
(4.9 Nm)
25 mm² [4 AWG]
insulation over the live part
AC
Chapter 4 Main Circuit Terminals | IED-S
Max.
Wire
Gauge
M6
36 mm²
[2 AWG]
Figure 1
4-5
Ground terminal:
Min.
Screw Size
Wire
and Tightening
Gauge
Torque (±10%)
16 mm² [6 AWG]
16 mm² [6 AWG]
50 kg-cm
(43.4 lb-in.)
(4.9 Nm)
16 mm² [6 AWG]
Figure 2
M6