Chapter 12 Descriptions of Parameter Settings | IED-S
Settings 0.0–510.0 V
 Sets this value according to the motor nameplate. If the motor is 220V, set this parameter to
220.0. If the motor is 200V, set this parameter to 200.0.
Motor Rated Current
Settings 0.10–650.00 Amps
 Sets this value according to the motor nameplate.
Motor Rated Power
Settings 0.10–650.00 kW
 Sets this value according to the motor nameplate.
Motor Rated Speed
Settings 0–65535 rpm
 Sets this value according to the motor nameplate.
 Speed (RPM) = (120 × Frequency) ÷ Number of Motor Poles
Number of Motor Poles
Settings 0–96
 Sets this value according to the motor nameplate.
 Sets the number of motor poles (must be an even number).
IM No-load Current
Settings 0.00–655.35
 This value is automatically measured after motor auto-tuning.
IM/PM Rs
IM Rr
Settings 0.000–65.535 Ω
 The values are automatically measured after motor auto-tuning.
IM Lm
IM Lx/PM Lq
Settings 0.0–6553.5 mH
 This value is automatically measured after motor auto-tuning.
PM Back Electromotive Force
Settings 0.0–6553.5 Vrms
 This value is automatically measured after motor auto-tuning.
PM Magnetic Pole Offset Angle
Settings 0.0–360.0°
 The offset angle between magnetic pole and PG origin (measured by auto-tuning)
12-13-2
Default: 2.00
Default: 2.00
Default: 0
Default: 0
Default: 0.00
Default: 0.000
Default: 0.0
Default: 0.0
Default: 360.0