Chapter 12 Descriptions of Parameter Settings | IED-S
PM Position Control Duration
Settings 0.000–65.535 sec.
 This setting is valid only when Pr.13-17 Bit7=1.
 Sets this parameter when elevator jerk occurs at start-up or car inversion occurs. In principle, the
duration cannot exceed the time when frequency starts output.
PM Position Control Gain (P)
Settings 0.00–655.00
 This setting is valid only when Pr.13-17 Bit7=1.
Forced Deceleration Limit
Settings 0000h–FFFFh
 Pr.13-61–Pr.13-65 require a software version 1.09 or above (see Pr.13-00) to work.
 The setting values are automatically generated after hoistway auto-tuning is finished. You can
also manually set them.
 Once forced deceleration switch is activated, protection will be triggered if the speed exceeds the
speed limit.
 The smaller the setting value, the easier protection is to be triggered. Once triggered, the
elevator runs slowly to the nearest floor to stop after elevator stops. The situation is automatically
cleared after elevator stops.
 When forced deceleration switch is activated, and the speed exceeds the speed limit setting, the
elevator decelerates to stop by using stronger forced deceleration and the following warning
codes occur:
1033: First one upward forced deceleration over-speed
1034: Second one upward forced deceleration over-speed
1035: Third one upward forced deceleration over-speed
1036: Fourth once upward forced deceleration over-speed
1037: First one downward forced deceleration over-speed
1038: Second one downward forced deceleration over-speed
1039: Third one downward forced deceleration over-speed
1040: Fourth one downward forced deceleration over-speed
First One Forced Deceleration Limit
Settings 0.00–99.99 m/s
 See Pr.13-16 parameter descriptions for details.
Second One Forced Deceleration Limit
Settings 0.00–99.99 m/s
 See Pr.13-16 parameter descriptions for details.
Bit 5=1: Enables forced deceleration switch speed limit (Pr.13-62–Pr.13-65)
protection function
12-13-14
Default: 0.000
Default: 80.00
Default: 0000h
Default: 1.00
Default: 2.00