 Sets the elevator's mode.
 LED display
Elevator Mode 1
Settings
 Sets the elevator's mode.
 LED display
Elevator Mode 2
Settings
bit 12: Car returns to the secondary landing at fire emergency
bit 13: Minor earthquake (Seismic P-wave)
bit 14: Small earthquake (Seismic S-wave)
bit 15: Severe earthquake
The display for digital keypad KPC-CC01
0000h–FFFFh
bit 0: Fault occurs
bit 1: Warning occurs
bit 2: FSD (Forced Stop Deceleration) mode
bit 3: Normal mode
bit 4: Evacuation mode
bit 5: Inspection mode
bit 6: Hoistway Auto-tuning
bit 7: Car returns to the main landing at fire emergency
bit 8: First class fireman
bit 9: Second class fireman
bit 10: Elevator lock mode
bit 11: UPS (Uninterruptible Power Supply) mode
bit 12: Earthquake mode
bit 13: Flood mode
bit 14: Overload mode
bit 15: Full-load mode
The display for digital keypad KPC-CC01
0000h–FFFFh
bit 0: VIP mode
bit 1: Attendant mode
bit 2: Auto-leveling after power-on again
bit 3: Car returns to the main landing for standby while idling
bit 4: Group control upward peak running
bit 5: Motor auto-tuning
bit 6: Group control downward peak running
bit 7: Automatic test for braking force once per day
bit 8: Group control peak running at random floor
bit 9: Set not to group control mode. Activate MI=161 ISS (Independent
Operation Switch) or set Pr.03-04 (Number of Group Control) to 0 can set not
to group control mode.
12-00-3
Chapter 12 Descriptions of Parameter Settings | IED-S
Default: Read only
Default: Read only