Setting
MI Function
Value
55
GOV (Governor)
56
DBP (Doorlock bypass)
BUNC (N.C. contact of brake unit (BU)
57
contactor)
IBRTS (Drive's discharge resistance
58
temperature switch)
59
UPK (Upward peak running)
60
DPK (Downward peak running)
61
SX1 (Door zone signal)
62
SX2 (Door unlock output feedback)
FXNO (N.O. contact of MPSCC
63
(Motor Phase Short Circuit
Contactor))
ERGO (Safety landing while severe
64
earthquake)
ULS4 (Fourth one upward forced
65
deceleration)
DLS4 (Fourth one downward forced
66
deceleration)
67
UPS (Uninterruptible Power Supply)
OLT1 (Front door reaches its open
100
position)
OLT2 (Rear door reaches its open
101
position)
CLT1 (Front door reaches its closed
102
position)
CLT2 (Rear door reaches its closed
103
position)
104
EDP1 (Front door light sensor)
105
EDP2 (Rear door light sensor)
Chapter 12 Descriptions of Parameter Settings | IED-S
UPS: The elevator must work with MI=125 BALWG
(Balanced switch) to execute safety landing. The
elevator executes downward safety landing when
BALWG is ON; executes upward safety landing
when BALWG is OFF.
Governor is normal when LED indicator is ON.
Doorlock bypass is the current status when LED
indicator is ON.
The N.C. contact of brake unit (BU) contactor. Used
to detect whether the BU contactor (relay) sticks or
not.
Discharge resistance temperature is normal when
LED indicator is ON.
Executes upward peak running when LED indicator
is ON.
Executes downward peak running when LED
indicator is ON.
The elevator is currently in the door zone when LED
indicator is ON.
1. When the elevator is leveling, door unlock output
feedback [SX2] ON is normal as long as door
unlock output [SY] is ON.
2. When the elevator is not in inspection mode, door
unlock output feedback [SX2] OFF is normal as
long as door unlock output [SY] is OFF.
3. When error occurs on item 1 and 2, UCMP board
is abnormal, and elevator cannot run.
The N.O. contact of MPSCC. Used to detect
whether FX contactor (relay) sticks or not.
Executes severe earthquake safety landing when
LED indicator is ON.
See description of MI=35 to MI=40.
Mains electricity is supplied by UPS when LED
indicator is ON.
Difference between EPS (MI=54) and UPS (MI=67):
EPS: The elevator can automatically determine to
execute upward safety landing or downward safety
landing.
UPS: The elevator must work with MI=125 BALWG
(Balanced switch) to execute safety landing. The
elevator executes downward safety landing when
BALWG is ON; executes upward safety landing
when BALWG is OFF.
The door is in its full open position when LED
indicator is ON. If you did not set this, door open
time by default is three seconds.
The door is in its full closed position when LED
indicator is ON.
An object is detected by the door light sensor when
LED indicator is ON. At this time, the door is unable
to act when door full close signal and doorlock
signal activate.
12-06-5
Description