Chapter 12 Descriptions of Parameter Settings | IED-S
3: 0011 announces as floor B1
4: 0100 announces as floor 1
5: 0101 announces as floor 2
If the bottom floor is B1, set Pr.03-57=3; if the bottom floor is B3, set Pr.03-57=1.
Door Unlock Board Test
Settings
 The setting automatically returns to 0 when the following conditions happen:
1.
When the elevator is not in emergency operation mode or in control panel inspection mode,
the warning code 1117 (Inspection, Unqualified, Door unlock board) occurs.
2.
When the layer door safety hatch and gate safety hatch signals do not change to ON in one
second after setting Pr.03-59 to 1, that is, you set Pr.03-59=1 while the door opens, the
warning code 1118 (Doorlock, Unqualified, Door unlock board) occurs.
3.
When the function test for door unlock board is not finished in 120 seconds, the warning
code 1119 (Door unlock board, Test, Overtime) occurs.
4.
When the function test for door unlock board is normal, the fault code F152 (Runs with door
open) occurs.
 The method for door unlock board test:
1.
Make the elevator stop at the leveling position, and keep the door closed.
2.
The elevator must be in emergency operation mode or in control panel inspection mode.
3.
Switch the test switch on the door unlock board to "TEST" to simulate that the door is open.
4.
Set Pr.03-59 (Door Unlock Board Test) to 1 to force the MO terminal Door Unlock Contactor
[SY] to be ON.
5.
Press and hold the upward operation or downward operation button for the manual mode. At
this time, the elevator runs a normal manual operation.
6.
When the elevator runs away from the leveling area, the door unlock board deactivates and
the doorlock of the brake contactor circuit short-circuits, further making both the door unlock
board and the brake contactor OFF. Then, the motor power is OFF, the brake is ON, the fault
code F152 (Runs with door open) occurs, and the elevator stops running.
Brake Test Duration
Settings
 Sets the duration of braking force test in seconds. If Pr.03-60=0, the automatic test for braking
force once per day does not run.
Brake Test Output Torque
Settings
 Sets the output torque during the braking force test.
Brake Test Moving Distance
Settings
 Sets the car moving distance during braking force test. If the car moving distance is larger than or
equal to Pr.03-62, the elevator stops and the fault code F150 (Unqualified braking force test)
occurs.
Brake Test Running Direction
Settings
0–1
0: Disabled
1: Runs the function test for door unlock board, and forces the multi-function
output (MO) terminal Door Unlock Contactor [SY] to be ON
0.0–20.0 sec.
0–200%
0.0–50.0 mm
0–1
0: Runs downward during braking force test
1: Runs upward during braking force test
12-03-12
Default: 0
Default: 5.0
Default: 100
Default: 5.0
Default: 1