Delta IED-S Series User Manual page 370

Integrated elevator drive
Table of Contents

Advertisement

1
Door closes, elevator begins to run, and
operation contactor and STO are ON
2
STO activation completed
3
Drive outputs, starting zero-speed begins
4
Brake contactor is ON
5
Starting zero-speed ends, and
acceleration begins
Suggested Setting Value:
Pr.03-18 (0.200 sec.) Delayed Time for
Leveling Switch
Pr.04-09 (1.5 m/s
2
) Inspection Deceleration
Pr.04-10 (0.2 m/s
2
) Inspection Acceleration
2
Pr.04-11 (0.1 m/s
) Re-leveling Deceleration
Methods of Accurate
Leveling for Direct
Docking:
1. Executes hoistway
auto-tuning
2. Executes upper and lower
re-leveling for each floor to
make leveling accurate.
3. Executes hoistway
auto-tuning again. Pr.04-03
(Hoistway Auto-tuning Speed)
should not be larger than 0.2
m/s.
Speed Control Timing Diagram – IM Direct Docking
6
Decelerates to zero speed, and
stopping zero-speed begins
7
Brake contactor is OFF
8
Stopping zero-speed ends, and
decreasing torque at stop begins
9
Decreasing torque at stop ends,
and drive stops outputting
Pr.05-25 (0.5 sec.) Door Open Delayed Time at Stop
Pr.13-42 (0.1 sec.) IM Mechanical Brake Release Delay
Time / PM Position Control Delay Time
Pr.13-43 (0.2 sec.) Mechanical Brake Engage Delay Time
Pr.13-44 (0.01 sec.) Drive Output Delay Time
NOTE:
1. If elevator starts with a jerk when brake releases, set Pr.13-54 (Zero Speed Activation Time) to 2.0 seconds,
and increase Pr.13-31 (Zero Speed at Start-up Bandwidth). Note that a too large Pr.13-31 value would cause
a jerk when elevator starts. It is suggested to increase Pr.13-31 to a value that elevator slightly shakes when
starting at top or bottom floor. Then, set Pr.13-31 = [(Pr.13-31 setting value -1) x 0.9], and set Pr.13-54 to
initial settings. In principle, set Pr.13-31 as large as possible, but cannot be too large that causes a jerk when
elevator starts. If jerk still occurs when brake releases, you can adjust Pr.13-44 (Drive Output Delay Time),
Pr.13-54 (Zero Speed Activation Time), and Pr.13-42 (IM Mechanical Brake Release Delay Time).
2. If brake engaged speed is slower, it may cause stopping zero-speed has already ended before brake
engages, further making motor run after stop and a jerk at stop occurs. In this case, set Pr.13-43 (Mechanical
Brake Engage Delay Time) to 0 first. If this problem still occurs, set Pr.13-55 (Zero Speed Stopping Time) to a
larger value.
3. If main motor starts to vibrate after brake is fully engaged, set Pr.13-57 (Time for Decreasing Torque at Stop)
to 5 seconds. If vibration reduces, change Pr.13-57 to a proper value. The larger the Pr.13-57 setting value,
the slower the elevator opens its door.
Chapter 12 Descriptions of Parameter Settings | IED-S
10
Pr.13-57 (Time for Decreasing Torque at Stop) is time that
triple rated current decreases to zero. The current of
stopping zero-speed is lower so it usually decreases to zero
in advance.
Operation contactor and STO are OFF
11
STO deactivation completed, and operation ends
12
Door begins to open
13
12-13-11
Pr.13-45 (0.01 sec.) Operation
Contactor Off Delay Time
Pr.13-54 (0.4 sec.) Zero Speed
Activation Time
Pr.13-55 (0.5 sec.) Zero Speed
Stopping Time
Pr.13-57 (0.0 sec.) Time for
Decreasing Torque at Stop