Chapter 12 Descriptions of Parameter Settings | IED-S
1
Door closes, elevator begins to run, and
operation contactor and STO are ON
2
STO activation completed
3
Drive outputs, starting zero-speed
begins, and brake contactor is ON
4
PM position control begins
5
PM position control ends
Suggested Setting Value:
Pr.03-18 (0.200 sec.) Delayed Time for
Leveling Switch
2
Pr.04-09 (1.5 m/s
) Inspection Deceleration
Pr.04-10 (0.2 m/s
2
) Inspection Acceleration
Pr.04-11 (0.1 m/s
2
) Re-leveling Deceleration
Pr.04-18 (3.0 sec.) Low-speed Running Time
When Enabled Manually
Methods of Accurate
Leveling for Direct
Docking:
1. Executes hoistway
auto-tuning
2. Executes upper and lower
re-leveling for each floor to
make leveling accurate.
3. Executes hoistway
auto-tuning again. Pr.04-03
(Hoistway Auto-tuning Speed)
should not be larger than 0.2
m/s.
Speed Control Timing Diagram – PM Direct Docking
6
Starting zero-speed ends, and
acceleration begins
7
Decelerates to zero speed, and
stopping zero-speed begins
8
Brake contactor is OFF
9
Stopping zero-speed ends, and
decreasing torque at stop begins
Pr.05-25 (0.5 sec.) Door Open Delayed Time at
Stop
Pr.13-42 (0.0 sec.) IM Mechanical Brake Release
Delay Time / PM Position Control Delay Time
Pr.13-43 (0.2 sec.) Mechanical Brake Engage
Delay Time
Pr.13-44 (0.01 sec.) Drive Output Delay Time
Pr.13-45 (0.01 sec.) Operation Contactor Off
Delay Time
NOTE:
1. If elevator starts with a jerk when brake releases, set Pr.13-54 (Zero Speed Activation Time) to 2.0 seconds,
Pr.13-58 (PM Position Control Duration) to 1.0 second, and increase Pr.13-31 (Zero Speed at Start-up
Bandwidth). Note that a too large Pr.13-31 value would cause a jerk when elevator starts. It is suggested to
increase Pr.13-31 to a value that elevator slightly shakes when starting at top or bottom floor. Then, set
Pr.13-31 = [(Pr.13-31 setting value -1) x 0.9], and set Pr.13-54 and Pr.13-58 to initial settings. In principle, set
Pr.13-31 as large as possible, but cannot be too large that causes a jerk when elevator starts.
2. If brake engaged speed is slower, it may cause stopping zero-speed has already ended before brake
engages, further making motor run after stop and a jerk at stop occurs. In this case, set Pr.13-43 (Mechanical
Brake Engage Delay Time) to 0 first. If this problem still occurs, set Pr.13-55 (Zero Speed Stopping Time) to a
larger value.
3. If main motor starts to vibrate after brake is fully engaged, set Pr.13-57 (Time for Decreasing Torque at Stop)
to 5 seconds. If vibration reduces, change Pr.13-57 to a proper value. The larger the Pr.13-57 setting value,
the slower the elevator opens its door.
Decreasing torque at stop ends, and drive stops outputting
10
Pr.13-57 (Time for Decreasing Torque at Stop) is time that
11
triple rated current decreases to zero. The current of stopping
zero-speed is lower so it usually decreases to zero in advance.
Operation contactor and STO are OFF
12
STO deactivation completed, and operation ends
13
Door begins to open
14
Pr.13-54 (0.4 sec.) Zero Speed Activation Time
Pr.13-55 (0.5 sec.) Zero Speed Stopping Time
Pr.13-57 (0.2 sec.) Time for Decreasing
Torque at Stop
Pr.13-58 (0.4 sec.) PM Position Control
Duration
Pr.13-59 (80.00) PM Position Control Gain (P)
12-13-8