Chapter 8 Specifications | IED-S
8-4 Operation, Storage and Transportation Environments
DO NOT expose the drive to a poor environment, such as one with dust, direct sunlight, corrosive or inflammable
gases, oil, humidity, liquids or excessive vibration. The salt in the air must be less than 0.01 mg/cm
Installation
Location
Surrounding
Temperature
Environment
Rated
Humidity
Altitude
Power
System
Storage
Package
Transportation
Drop
 1.0 mm, peak-to-peak value range from 2–13.2 Hz
Vibration
 0.7–1.0 G, range from 13.2–55 Hz
Compliance with IEC 60068-2-6
Impact
Compliance with IEC/EN 60068-2-27
Protection
IP00
Level
EMC Level
IEC 61800-3 and IEC 61000-4
*1: TN system: The neutral point of the power system connects directly to the ground. The exposed metal components connect to
the ground through the protective grounding conductor.
*2: Single-phase models use a single-phase three-wire power system.
IEC60364-1/IEC60664-1 pollution degree 2. Indoor use only.
-10–40°C, up to 50°C with derating for the operating temperature
40–50°C
Operation
with
Derating
Storage /
-20–60°C
Transportation
Non-condensing, non-freezing
Operation
Max. 90%
Storage /
Max. 90%
Transportation
Non-condensing, non-freezing
If the drive is installed at an altitude of 0–1000 m, follow normal
operation restrictions. For altitudes of 1000–3000 m, decrease the
drive's rated current by 1% or lower the temperature by 0.5°C for every
Operation
100 m increase in altitude. The maximum altitude for corner grounding
is 3000 m. If installing at an altitude higher than 3000 m is required,
contact Delta for more information.
TN system
*1*2
ISTA procedure 1A (according to weight) IEC60068-2-31
5.5–30 kW: for every 1°C increase in temperature,
decrease the drive's rated current by 2.5%
37–75 kW: for every 1°C increase in temperature,
decrease the drive's rated current by 2.0%
8-4
2
every year.