Chapter 12 Descriptions of Parameter Settings | IED-S
VIP Standby Time
Settings
No
Clear all hall calls and no new hall calls can be registered.
The setting value of Pr.03-33 is the VIP floor.
Check if Pr.03-34 (VIP Car Call Limit) = 1
Buttons from car & hall calls at VIP floor automatically light on.
Check if Pr.03-34 (VIP Car Call Limit) = 1
VIP mode
Yes
ends
Elevator runs towards the desired floor
Check if elevator arrives the desired floor
0–65535 sec.
VIP Operation Flow Chart
Normal Mode
No
Check if there is any floor
specified by Pr.03-33 (VIP Floor)
Yes
Check if MI=164 VIP
(VIP mode) is set
Yes
Check if MI=164 (VIP) changes
from OFF to ON
Yes
Yes
Clear all car calls and no new car calls
can be registered.
"Vip" displays on floor display board.
Yes
Check if elevator arrives VIP floor
Yes
Elevator stops at VIP floor. Check if
exceeds Pr.03-32 (VIP Standby Time).
NO
Check if car call button is
pressed for the desired floor
Yes
Check if elevator door closes
Yes
Yes
VIP mode
ends
Check if Pr.03-36 (HCB J4 Pin3&4 Function)=3 (VIP) and J4
Pin3&4 on hall call board are short-circuited at certain floor
No
Check if Pr.03-35 (HCB J4 Pin1&2 Function)=3 (VIP) and J4
No
Pin1&2 on hall call board are short-circuited at certain floor
Check if both Pr.03-35 (HCB J4 Pin1&2 Function) and Pr.03-
No
36 (HCB J4 Pin3&4 Function) are not set to 3 (VIP)
Yes
Check if the hall call button is pressed at floor
specified by Pr.03-33 (VIP Floor)
Yes
Floor that J4 is short-circuited becomes VIP floor
No
Check if elevator finishes responding
No
to all car calls and door is closed
Yes
Elevator runs
No
towards VIP floor
Elevator door
No
remains open
No
NO
12-03-6
Default: 40
Yes
Yes
No
No
Normal Mode
Car call is used as
No
normal mode.
VIP mode
ends