Brake Test Time (Hour)
Settings
 Sets the time (hour) to run the automatic braking force test once per day.
Brake Test Time (Minute)
Settings
 Sets the time (minute) to run the automatic braking force test once per day.
Brake Test Floor
Settings
 Sets the physical floor to run the automatic braking force test once per day. If Pr.03-66=0, the test
runs at the floor where the elevator stops.
Brake Test Starting
Settings
 If Pr.03-67=1, the manual braking force test starts to run. The setting automatically returns to 0
once the test is finished or the test failed.
 Manual braking force test
1.
Set the time (seconds) to run the braking force test in Pr.03-60 (Brake Test Duration),
ranging from 0.0 to 20.0 seconds.
2.
Set the output torque to run the braking force test in Pr.03-61 (Brake Test Output Torque),
ranging from 0% to 200%.
3.
Set the car moving distance during braking force test in Pr.03-62 (Brake Test Moving
Distance), ranging from 0.0 to 50.0 mm.
4.
Set Pr.03-63 (Brake Test Running Direction). If Pr.03-63=1, the elevator runs upward during
braking force test. If Pr.03-63=0, the elevator runs downward during braking force test.
5.
Make the elevator car stop at the leveling position, and the elevator must be in emergency
operation mode or in control panel inspection mode. Moreover, ensure that there is no fault
occurred, and upward operation or downward operation button for the manual mode is not
allowed to press.
6.
Set Pr.03-67 (Brake Test Starting) =1 to start the braking force test. If the condition does not
meet the fifth description above, Pr.03-67 immediately returns to 0 after setting to 1, and the
following warning codes occur: 1110 (Inspection, Unqualified, Braking force), or 1111
(Leveling, Unqualified, Braking force), or 1113 (Fault, Unqualified, Braking force), or 1114
(Button, Unqualified, Braking force). However, if the condition meet the fifth description
above, warning codes 1115 (Wait, Braking force test) or 1109 (Braking force, Under test)
occurs.
If the door does not close after setting Pr.03-67=1, the warning code 1115 (Wait, Braking
force test) occurs, and then the door closes automatically. After the door closes, the warning
code 1109 (Braking force, Under test) occurs. Then, the operation contactor outputs
automatically, the brake contactor does not output, torque outputs and gradually increases
to Pr.03-61 (Brake Test Output Torque) setting value.
7.
If the car moving distance is not smaller than Pr.03-62 (Brake Test Moving Distance) within
Pr.03-60 (Brake Test Duration) setting time, the test stops automatically and the fault code
F150 (Unqualified braking force test) occurs. At this time, you must press the external reset
device in the manual mode, or press the RESET key on the digital keypad in the manual
mode, or press and hold both the upward operation and downward operation buttons
simultaneously in the manual mode for more than five seconds to reset the fault code F150.
If the car moving distance is smaller than Pr.03-62 (Brake Test Moving Distance), and time
exceeds Pr.03-60 (Brake Test During), the test also stops automatically and the warning
code 1112 (Braking force, Test, Qualified) occurs.
8.
Once the braking force test is finished, Pr.03-67 (Brake Test Starting) automatically returns
to 0. The elevator runs automatically only when the braking force test is qualified. Otherwise,
0–23
0–59
0–64
0–1
12-03-13
Chapter 12 Descriptions of Parameter Settings | IED-S
Default: 2
Default: 59
Default: 0
Default: 0