Chapter 12 Descriptions of Parameter Settings | IED-S
Inspection Deceleration
Settings 0.500–3.000 m/s
 Setting a too low value may cause runaway while adjusting position during return to two ends of
the hoistway.
Inspection Acceleration
Settings 0.10–1.50 m/s
Re-leveling Deceleration
Settings 0.10–1.50 m/s
Acceleration Begin Time S1
Settings 0.01–25.00 sec.
Acceleration Arrival Time S2
Settings 0.01–25.00 sec.
Deceleration Begin Time S3
Settings 0.01–25.00 sec.
Deceleration Arrival Time S4
Settings 0.01–25.00 sec.
Low-speed Running Time When Enabled Manually
Settings 0.0–10.0 sec.
 When enabling manually, the elevator runs at leveling speed within Pr.04-18 setting time first,
and then runs at inspection speed.
2
2
2
12-04-2
Default: 2.000
Default: 0.20
Default: 1.50
Default: 3.00
Default: 1.00
Default: 1.00
Default: 3.00
Default: 3.0