Fault Name
Fault occurs when SFNC (N.C. contact of safety hatch
SFNC ON error
contactor) is not OFF after safety hatch contactor
activates (ON)
Action and Reset
Stops urgently
MI=17 SFNC (N.C. contact of safety hatch contactor)
Press the upward or downward operation button for the manual mode, press the
RESET key on the digital keypad, press the external reset device, or power-on
again (choose either)
Fault Name
Fault occurs when SFNC (N.C. contact of safety hatch
SFNC OFF error
contactor) is not ON after safety hatch contactor
deactivates (OFF)
Action and Reset
Stops urgently
MI=17 SFNC (N.C. contact of safety hatch contactor)
Press the upward or downward operation button for the manual mode, press the
RESET key on the digital keypad, press the external reset device, or power-on
again (choose either)
Fault Name
Fault occurs when the highest floor is not identical to the
Mismatched highest
highest physical floor set in Pr.03-01 after finishing
floor
hoistway auto-tuning
Action and Reset
Stops urgently
Pr.03-01 (Highest Physical Floor)
Switch to the manual mode
Fault Name
Fault occurs when SX1 (Door one signal) and FL1
Door zone MI setting
(Upper door zone sensor) or FL2 (Lower door zone
error
sensor) are all enabled, or either of FL1 FL2 is enabled
after 60 seconds
Action and Reset
Stops urgently
MI=61 SX1 (Door zone signal)
MI=3 FL1 (Upper door zone sensor)
MI=4 FL2 (Lower door zone sensor)
Resets automatically once the setting is normal
14-3
Chapter 14 Fault Codes | IED-S