Chapter 12 Descriptions of Parameter Settings | IED-S
0: Not in INSCP (control panel inspection switch) or EIS (electrical operation)
mode
2: Still in inspection mode after setting Pr.03-00 (Hoistway Auto-tuning) = 1
3: Switch inspection switch to auto
10: Door does not close
11: Elevator starts to run downward
12: Elevator runs downward, first one downward forced deceleration (DLS1)
is ON
13: Elevator runs downward, first one downward forced deceleration (DLS1)
is ON
14: Elevator runs downward, first one downward forced deceleration (DLS1)
and leveling sensor are ON
15: Lower leveling sensor (DZD) is ON, door zone signal (SX1) and upper
leveling sensor (DZU) are OFF
16: Lower leveling sensor (DZD) and door zone signal (SX1) are ON, upper
leveling sensor (DZU) is OFF
17: Lower leveling sensor (DZD), door zone signal (SX1), and upper leveling
sensor (DZU) are all ON
18: Lower leveling sensor (DZD) is OFF, door zone signal (SX1) and upper
leveling sensor (DZU) are ON
19: Lower leveling sensor (DZD) and door zone signal (SX1) are OFF, upper
leveling sensor (DZU) is ON
20: Lower leveling sensor (DZD), door zone signal (SX1), and upper leveling
sensor (DZU) are all OFF
21: Lower limit switch (LSD) is ON
24: Lower limit switch (LSD) is ON
25: Lower limit switch (LSD) is ON for more than 2 seconds
26: Elevator starts to run upward
27: Elevator runs upwards, first one upward forced deceleration (ULS1) is ON
28: Elevator runs upwards, first one upward forced deceleration (ULS1) is ON
29: Elevator runs upward, first one upward forced deceleration (ULS1) and
leveling sensor are ON
30: Elevator runs upward, first one upward forced deceleration (ULS1) and
leveling sensor are ON
31: Upper limit switch (LSU) is ON
32: Upper limit switch (LSU) is ON
33: Upper limit switch (LSU) is ON for more than 1 second
34: Upper limit switch (LSU) is ON for more than 1.5 seconds
35: Upper limit switch (LSU) is ON for more than 2 seconds
36: Upper limit switch (LSU) is ON for more than 2 seconds
37: Elevator stops at leveling (level) for more than 2 seconds
38: Elevator stops at leveling (level) for more than 2 seconds
39: Hoistway auto-tuning ended
200 (Error): Set Pr.03-00 = 1 when error occurs
201 (Error): Set Pr.03-00 = 1 when Pr.03-01 = 1 (Highest Physical Floor)
202 (Error): Change inspection switch to manual during hoistway auto-tuning
process
203 (Error): Press inspection upward or downward button during hoistway
auto-tuning process
204 (Error): Lower limit switch (LSD) is installed too low. Lower limit switch
(LSD) activates after upper leveling sensor (DZU) is OFF
205 (Error): Lower limit switch (LSD) is installed too low. Lower limit switch
(LSD) activates after upper leveling sensor (DZU) is OFF
206 (Error): Lower limit switch (LSD) is ON, first one downward forced
deceleration (DLS1) is not ON
207 (Error): Upper limit switch (LSU) is ON, lower leveling sensor (DZD) is not
ON
208 (Error): Upper limit switch (LSU) is ON, first one upward forced
deceleration (ULS1) is not ON
12-00-12