Chapter 14 Fault Codes | IED-S
Code#
KPC-CC01 Display
F131
Action
Related Parameters
Reset Method
Code#
KPC-CC01 Display
F132
Action
Related Parameters
Reset Method
Code#
KPC-CC01 Display
F133
Action
Related Parameters
Reset Method
Code#
KPC-CC01 Display
F134
Action
Related Parameters
Reset Method
Fault Name
Fault occurs when BUNC (N.C. contact of brake unit
BUNC ON error
(BU) contactor) is not OFF after BU (Contactor of brake
unit) activates (ON)
Action and Reset
Stops urgently
MO=7 BU (Contactor of brake unit)
MI=57 BUNC (N.C. contact of brake unit (BU) contactor)
Press the upward or downward operation button for the manual mode, press the
RESET key on the digital keypad, press the external reset device, or power-on
again (choose either)
Fault Name
Fault occurs when BUNC (N.C. contact of brake unit
BUNC OFF error
(BU) contactor) is not ON after BU (Contactor of brake
unit) deactivates (OFF)
Action and Reset
Stops urgently
MO=7 BU (Contactor of brake unit)
MI=57 BUNC (N.C. contact of brake unit (BU) contactor)
Press the upward or downward operation button for the manual mode, press the
RESET key on the digital keypad, press the external reset device, or power-on
again (choose either)
Fault Name
Error detected when both DZU and DZD are ON but
Door zone signal OFF
door zone sensors are OFF (SX1 is not ON, or either of
error
FL1 and FL2 is not ON). Fault code occurs until elevator
stops and, at this time, elevator cannot run.
Action and Reset
Stops urgently
MI=1 DZU (Upper leveling sensor)
MI=2 DZD (Lower leveling sensor)
MI=3 FL1 (Upper door zone sensor)
MI=4 FL2 (Lower door zone sensor)
MI=61 SX1 (Door zone signal)
Make all door zone sensors ON or switch to the manual mode
Fault Name
Error detected when both DZU and DZD are OFF but
Door zone signal ON
door zone sensors are ON (SX1 is not OFF, or either of
error
FL1 and FL2 is not OFF). Fault code occurs until
elevator stops and, at this time, elevator cannot run.
Action and Reset
Stops urgently
MI=1 DZU (Upper leveling sensor)
MI=2 DZD (Lower leveling sensor)
MI=3 FL1 (Upper door zone sensor)
MI=4 FL2 (Lower door zone sensor)
MI=61 SX1 (Door zone signal)
Make all door zone sensors OFF or switch to the manual mode
14-6
Description
Description
Description
Description