Motor Parameters Auto Tuning; Motor Line-To-Line Resistance R1 - Delta VFD-B User Manual

High performance user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B:
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-B Series
07 - 05

Motor Parameters Auto Tuning

Settings
Start Auto Tuning by pressing RUN key after this parameter is set to 01 or 02.
When set to 01, it will only auto detect R1 value and Pr.07-01 must be input manually. When
set to 02, the AC motor drive should be unloaded and the values of Pr.07-01 and Pr.07-06 will
be set automatically.
The steps to AUTO-Tuning are:
1.
Make sure that all the parameters are set to factory settings and the motor wiring is
correct.
2.
Make sure the motor has no-load before executing auto-tuning and the shaft is not
connected to any belt or gear motor.
3.
Fill in Pr.01-01, Pr.01-02, Pr.07-00, Pr.07-04 and Pr.07-08 with correct values.
4.
After Pr.07-05 is set to 2, the AC motor drive will execute auto-tuning immediately after
receiving a "RUN" command. (Note: The motor will run!). The total auto tune time will be
15 seconds + Pr.01-09 + Pr.01-10. Higher power drives need longer Accel/|Decel time
(factory setting is recommended). After executing, Pr.07-05 is set to 0.
5.
After successful execution, the drive will set Pr.07-01 and Pr.07-06 accordingly. If not,
repeat steps 3 and 4.
6.
Then you can set Pr.00-09 to 02/03 and set other parameters according to your
application requirement.
NOTE
1. In vector control mode it is not recommended to have motors run in parallel.
2. It is not recommended to use vector control mode if motor rated power exceeds the rated power of
the AC motor drive.
07 - 06

Motor Line-to-line Resistance R1

Settings
The motor auto tune procedure will set this parameter. The user may also set this parameter
without using Pr.07-05.
07 - 07
Reserved
5-72
00
Disable
01
Auto Tuning R1 (motor doesn't run)
02
Auto Tuning R1 + No-load Test (with running motor)
00 to 65535 mΩ
Factory Setting: 00
Factory Setting: 00
Revision July 2008, BE16, SW V4.08 & V5.00
Unit: 1
Unit: 1