Chapter 12 Descriptions of Parameter Settings | IED-S
Door Open/Close Mode when in Manual Operation
Settings
0: The door opening/closing signal does not output if they are NOT in the conditions below.
The door opens when:
1. The elevator stops in the leveling area, and you press the upward and downward operation
buttons for the manual mode simultaneously.
2. The elevator stops in the non-leveling area, and you press the UP and DOWN buttons in the
car simultaneously when the elevator is in the car inspection mode.
The door closes when:
1. The elevator is running.
2. You press the upward or downward operation button for the manual mode respectively.
No matter what you set in Pr.05-24 for the manual mode, the following door opening/closing may
still occur even the elevator stops in the non-leveling area:
The front door opens when MI=121 DOBOC1 (Cartop inspection front door opening button)
activates;
The rear door opens when MI122 DOBOC2 (Cartop inspection rear door opening button)
activates;
The front door closes when MI123 DCBOC1 (Cartop inspection front door closing button)
activates;
The rear door closes when MI124 DCBOC2 (Cartop inspection rear door closing button)
activates.
Door Open Delayed Time at Stop
Settings
Sets the door open delayed time when elevator stops at leveling and after operation contactor
deactivates.
If you have already set Pr.03-20 (Door Pre-open at Stop), door open time is not affected by
Pr.05-25 (Pr.05-25 is invalid).
Closing Time for Door Open Signal
Settings
Closing Time for Door Close Signal
Settings
0–2
0: Door open/close signal does not output
1: The door does not open, and automatically closes if the door is not closing.
2: The door opens automatically when the elevator stops in the leveling area;
the door closes when you press the upward or downward operation button for
the manual mode respectively.
0.0–2.0 sec.
0.0–600.0 sec.
0.0: The door opening signal outputs continuously
0.1–600.0: Starts to count the time after the door opens to its full position. The
door opening signal stops output when the counting time exceeds Pr.05-26.
0.0–600.0 sec.
0.0: The door closing signal outputs continuously
0.1–600.0: Starts to count the time after the door closes. The door closing
signal stops output when the counting time exceeds Pr.05-27.
12-05-4
Default: 0
Default: 0.5
Default: 0.0
Default: 0.0