Chapter 12 Descriptions of Parameter Settings | IED-S
Door Open/Close Mode when in Manual Operation
Settings
 0: The door opening/closing signal does not output if they are NOT in the conditions below.
The door opens when:
1. The elevator stops in the leveling area, and you press the upward and downward operation
buttons for the manual mode simultaneously.
2. The elevator stops in the non-leveling area, and you press the UP and DOWN buttons in the
car simultaneously when the elevator is in the car inspection mode.
The door closes when:
1. The elevator is running.
2. You press the upward or downward operation button for the manual mode respectively.
 No matter what you set in Pr.05-24 for the manual mode, the following door opening/closing may
still occur even the elevator stops in the non-leveling area:
The front door opens when MI=121 DOBOC1 (Cartop inspection front door opening button)
activates;
The rear door opens when MI122 DOBOC2 (Cartop inspection rear door opening button)
activates;
The front door closes when MI123 DCBOC1 (Cartop inspection front door closing button)
activates;
The rear door closes when MI124 DCBOC2 (Cartop inspection rear door closing button)
activates.
Door Open Delayed Time at Stop
Settings
 Sets the door open delayed time when elevator stops at leveling and after operation contactor
deactivates.
 If you have already set Pr.03-20 (Door Pre-open at Stop), door open time is not affected by
Pr.05-25 (Pr.05-25 is invalid).
Closing Time for Door Open Signal
Settings
Closing Time for Door Close Signal
Settings
0–2
0: Door open/close signal does not output
1: The door does not open, and automatically closes if the door is not closing.
2: The door opens automatically when the elevator stops in the leveling area;
the door closes when you press the upward or downward operation button for
the manual mode respectively.
0.0–2.0 sec.
0.0–600.0 sec.
0.0: The door opening signal outputs continuously
0.1–600.0: Starts to count the time after the door opens to its full position. The
door opening signal stops output when the counting time exceeds Pr.05-26.
0.0–600.0 sec.
0.0: The door closing signal outputs continuously
0.1–600.0: Starts to count the time after the door closes. The door closing
signal stops output when the counting time exceeds Pr.05-27.
12-05-4
Default: 0
Default: 0.5
Default: 0.0
Default: 0.0