Chapter 3 Wiring | IED-S
14-2 Hall Call Board Connected to Normal Call, Elevator Lock (Shutdown), and Fire Alarm Recall
Hall call function settings:
1. Switch SW2 to SET to start the settings.
2. Press DOWN when the floor position displays 0. Press DOWN again to change the mode selection
of the arrow position. Then, press UP to add 1 to the station number of floor position.
3. There are seven modes in total: Car (M), Front Door (F), Rear Door (B), Front Door Disability (F
Rear Door Disability (B
Lantern & Chime (B
4. If the floor position indicator is not 0, press UP or DOWN to set the floor station number.
5. The floor station number is set according to the physical floor. For example, if the current floor is B1F
to 10F, then set B1F to station number 1, 1F to station number 2, and so on.
6. If used as the floor display board for the car, set the mode to M.
7. If the current setting is 5F front door hall call, and you need to change it to 4F front door disability. In
this case, you must return the floor station number to 0 first, then you can change the mode and set
the floor station number.
Station Number Setting
), Front Door Directional Lantern & Chime (F
)
●●
F 1–64 Normal Front Door
B 1–64 Normal Rear Door
3-22
), Rear Door Directional
●●
),