Chapter 12 Descriptions of Parameter Settings | IED-S
the fault code F150 (Unqualified braking force test) occurs when changing the inspection
switch to automatic mode, and the elevator does not run.
 Automatic braking force test once per day
1.
Set the time (seconds) to run the braking force test in Pr.03-60 (Brake Test Duration),
ranging from 0.0 to 20.0 seconds. If Pr.03-60=0, the automatic test for braking force once
per day does not run.
2.
Set the output torque to run the braking force test in Pr.03-61 (Brake Test Output Torque),
ranging from 0% to 200%.
3.
Set the car moving distance during braking force test in Pr.03-62 (Brake Test Moving
Distance), ranging from 0.0 to 50.0 mm
4.
Set Pr.03-63 (Brake Test Running Direction). If Pr.03-63=1, the elevator runs upward during
braking force test. If Pr.03-63=0, the elevator runs downward during braking force test.
5.
Set the time to run the automatic braking force test once per day in Pr.03-64 (Brake Test
Time (Hour)) and Pr.03-65 (Brake Test Time (Minute)).
6.
Set the physical floor to run the automatic braking force test in Pr.03-66 (Brake Test Floor),
ranging from 0 to 64 floors.
7.
After finishing the setting, the elevator automatically runs to the designated floor (the
warning code 1116 (Recall, Braking force test) occurs) in the specified time every day while
idling (if the warning code 1115 (Wait, Braking force test) occurs during the elevator's
running) to run the upward or downward braking force test (the warning code 1109 (Braking
force, Under test) occurs) with the brake OFF. In the process of test, car call cannot register
any call; hall call can register but not respond to the calls.
8.
If the test result is qualified, the elevator returns to normal mode and the warning code 1112
(Braking force, Test, Qualified) occurs. But if the car moving distance is not smaller than
Pr.03-62 (Brake Test Moving Distance), the elevator malfunctions and is unavailable, and
the fault code F150 (Unqualified braking force test) occurs. At this time, change to the
manual mode first, and then press the external reset device, or press the RESET key on the
digital keypad, or press and hold both the upward operation and downward operation
buttons simultaneously for more than five seconds to reset the fault code F150. Moreover,
use the methods described in the "Manual braking force test" section above until the warning
code 1112 (Braking force, Test, Qualified) appears to make the elevator run automatically.
Otherwise, the fault code F150 (Unqualified braking force test) remains when changing from
manual to automatic mode, and the elevator does not run.
First Main Group Control
Second Main Group Control
Third Main Group Control
Fourth Main Group Control
Fifth Main Group Control
Sixth Main Group Control
Seventh Main Group Control
Settings 0–63S
Dispersed Waiting
Settings
 Sets the idle time that elevator automatically runs dispersed waiting.
 Goal: To make elevator arrive within ten seconds when there is hall call from any floor in off-peak
hours
 Method:
1. In parallel control, when normally there are at least two running elevators and Pr.03-75 is not
set to 0, you can execute dispersed waiting.
2. After elevator finishes responding to all car/hall calls in group control operation, time starts to
0–65535 sec.
12-03-14
Default: 0
Default: 0