10-3-5 Contacts of IED-S Cartop Board
Pr.07-99 Clear Contacts of Cartop Board
Due to the uniqueness of MI contacts, you can set Pr.07-99 to clear all default values of MI/MO
contacts if the wiring of contacts for the main control board on-site is different from those shown
in Section 10-3-1 and 10-3-2.
 Setting values:
0: No function
1: Set all MI contacts of the cartop board to 0
2: Set all MO contacts of the cartop board to 0
3: Set all values in Parameter Group 07 to 0
Pr.07-XX Contacts of Cartop Board
 Setting the setting value to thousands digit changes the contact from N.O. to N.C. or vice
versa.
For example, if you set DZU (Upper Leveling Sensor) to 1, the contact is N.O. (Normally
Open); if you set DZU (Upper Leveling Sensor) to 1001, the contact becomes N.C.
(Normally Closed).
 The function of MI contacts is unique, that is, you cannot enter the same value into different
parameters simultaneously (even across Parameter Group 06 and 07).