Time for No Response to Hall Calls
Settings
 When the elevator door opens, the elevator does not respond to the hall call at the current floor
during Pr.05-28 setting time. This is to prevent the following conditions from happening:
1. Hall call buttons are stuck.
2. The door re-opens due to passengers' pressing the buttons at the hall call while the elevator
is in full load and in door closing status.
3. The door re-opens due to hall calls from passengers who arrive the landing hall later than
those already in the elevator car.
 If Pr.05-28=0, this function is disabled.
0–60 sec.
12-05-5
Chapter 12 Descriptions of Parameter Settings | IED-S
Default: 0