Door Control - Delta IED-S Series User Manual

Integrated elevator drive
Table of Contents

Advertisement

Chapter 12 Descriptions of Parameter Settings

05 Door Control

Number of Doors
Settings 1–2
 1: Controls one door
 2: Control two doors
Door Open Control
Settings 0–2
DSF 16–1
DSF 32–17
DSF 48–33
DSF 64–49
Settings 0–65535
 Serviced physical floor 1S–64S at the front door.
 Uses 16-bit setting for every sixteen floor. If the bit setting that corresponds to the floor is 1, the
elevator responds to the front door of the floor. If the bit setting that corresponds to the floor is 0,
the elevator does not respond to the front door of the floor.
 For example, in a building with elevator of ten floors, if you need to set the elevator not respond
to the front doors at 3F and 5F, which corresponds to bit2 and bit4 respectively, set Pr.05-02 to
65515 (0xFFEB) [=65535-2
 Setting method of LED display
DSB 16–1
DSB 32–17
DSB 48–33
DSB 64–49
Settings
1: Single-door system
2: Two-door system
0: Door does not open
1: Front door opens before rear door opens
2: Font and rear door open at the same time
-2
2
4
]. Use the same setting method for similar parameters.
Setting method of digital keypad KPC-CC01
0–65535
12-05-1
Chapter 12 Descriptions of Parameter Settings | IED-S
: You can set this parameter during operation.
Default: 1
Default: 1
Default: 65535
Default: 0