32: DWEZ Analog Input 3
Setting Value
Function
32
DWEZ Analog Input 3

H4: Analog Outputs

H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
• H4-02 [Terminal FM Analog Output Gain]
• H4-03 [Terminal FM Analog Output Bias]
• H4-05 [Terminal AM Analog Output Gain]
• H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08 [Terminal AM Signal Level Select] to select
the voltage output and current output.
No.
H4-02
Terminal FM Analog Output Gain
H4-03
Terminal FM Analog Output Bias
H4-05
Terminal AM Analog Output Gain
H4-06
Terminal AM Analog Output Bias
H4-07
Terminal FM Signal Level Select
H4-08
Terminal AM Signal Level Select
Figure 2.110
and
Figure 2.111
For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal FM, H4-03
[Terminal FM Analog Output Bias] is set to 30%.
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Name
show the gain and bias.
Figure 2.110 Analog Output Gain/Bias Configuration Example 1
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Range
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
2.8 H: Terminal Functions
Default
100.0%
0.0%
50.0%
0.0%
0
0
419
2