F1-50: PG-F3 Option Encoder Type
No.
Name
(Hex.)
F1-50
PG-F3 Option Encoder Type
(03D2)
0 : EnDat Sin/Cos
1 : EnDat Serial Only
2 : HIPERFACE
F1-51: PG-F3 PGoH Detection Level
No.
Name
(Hex.)
F1-51
PG-F3 PGoH Detection
Level
(03D3)
The drive will detect PGoH if the value of this parameter is smaller than the value of
Regarding the expression
the single-track (phase A) output from the encoder.
Note:
This function is enabled when F1-20 = 1 [Encoder 1 PCB Disconnect Detect = Enabled].
F1-52: Serial Encoder Comm Speed
No.
Name
(Hex.)
F1-52
Serial Encoder Comm Speed
(03D4)
Note:
This function is enabled when F1-50 = 1 or 2 [PG-F3 Option Encoder Type = EnDat Serial Only or HIPERFACE].
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps

F2: Analog Input Option

F2 parameters set the operation of the drive when you use analog input option card AI-A3. The AI-A3 card has 3
input terminals that accept voltages of -10 V to +10 V (20 kΩ) or currents of 4 mA to 20 mA (250 Ω). Install the AI-
A3 card to enable setting very accurate analog references with high resolution.
Refer to the AI-A3 option manual for more information about how to install, wire, and set the AI-A3 card.
WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
F2-01: Analog Input Function Selection
No.
Name
(Hex.)
F2-01
Analog Input Function
Selection
(038F)
Note:
When the AI-A3 card is not mounted in the drive, analog input terminals A1 to A3 on the drive are always enabled. The setting of this
parameter does not have an effect.
0 : 3 Independent Channels
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of encoder connected to the PG-F3 option.
V/f
CL-V/f
OLV
CLV
AOLV
The drive will detect PGoH [Encoder (PG) Hardware Fault] if the value of this parameter is smaller
than the value of
, Sin θ is the single-track (phase B) output from the encoder and Cos θ is
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communication speed between the PG-F3 option and the serial encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the analog reference used with AI-A3.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.7 F: Options
Default
(Range)
0
(0 - 2)
Default
(Range)
80%
(1 - 100%)
.
Default
(Range)
0
(0 - 2)
Default
(Range)
0
(0, 1)
2
323