YASKAWA GA800 Programming Manual page 398

Ac drive for industrial applications
Table of Contents

Advertisement

2.8 H: Terminal Functions
18: Torque Detection 2 (N.O.)
Setting Value
Function
18
Torque Detection 2 (N.O.)
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level
2], or the level is less than the torque value set with L6-05 for longer than the time set with L6-06
[Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time set in
L6-06.
• Refer to "L6: Torque Detection" for more information.
19: Torque Detection 2 (N.C.)
Setting Value
Function
19
Torque Detection 2 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection
Level 2], or the level is less than the torque value set with L6-05 for longer than the time set with L6-
06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time set in
L6-06.
• Refer to "L6: Torque Detection" for more information.
1A: During Reverse
Setting Value
Function
1A
During reverse
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
1B: During Baseblock (N.C.)
Setting Value
Function
1B
During Baseblock (N.C.)
ON : The drive is not in baseblock.
398
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor operates in the reverse direction.
Figure 2.99 Reverse Operation Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming

Advertisement

Table of Contents
loading