This calibration function lets the drive suppress the torque ripple of a motor. Usually it is not necessary to change this
setting.
0 : No Calibration
1 : One Time Calibrate at Next Start
2 : Calibrate Every Time at Start
n1-16: Hunting Prevention High Fc Gain
No.
Name
(Hex.)
n1-16
Hunting Prevention High Fc
Gain
(0BFB)
Expert
Set n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)] to enable this function.
If the motor oscillates, set n1-01 = 2. If that does not have an effect, increase this parameter in 0.2-unit increments.
n1-17: Hunting Prevent High Fc Filter
No.
Name
(Hex.)
n1-17
Hunting Prevent High Fc
Filter
(0BFC)
Expert
When n1-01 = 2 [Hunting Prevention Selection = Enabled (High Carrier Frequency)], if the motor stalls when the
load changes, increase the value set in this parameter in 100 ms increments.
If you set n1-01 = 2 and you cannot suppress hunting, increase the value set in this parameter in 100 ms increments.
n1-20: Voltage Calibration Duration
No.
Name
(Hex.)
n1-20
Voltage Calibration Duration
(1588)
Expert

n2: Auto Freq Regulator (AFR)

The speed feedback detection reduction function (or AFR: Automatic Frequency Regulator) helps the speed become
stable when you suddenly apply or remove a load.
Note:
Before you change n2-xx parameters, do one of these procedures:
• Set the motor parameters and V/f pattern correctly.
• Do Rotational Auto-Tuning.
n2-01: Automatic Freq Regulator Gain
No.
Name
(Hex.)
n2-01
Automatic Freq Regulator
Gain
(0584)
Adjust this parameter in these conditions:
• If hunting or oscillation occurs with light loads, increase the setting value in 0.05-unit increments and examine the
response.
• When torque is not sufficient with heavy loads or to make the torque or speed response better, decrease the setting
value in 0.05-unit increments and examine the response.
486
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the hunting prevention function. This parameter functions best with a high carrier
frequency. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the hunting prevention function. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the calibration time at start. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to change this
setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
Determined by o2-04
(0.00 - 2.50)
Default
(Range)
500 ms
(0 - 1000 ms)
Default
(Range)
50 ms
(10 - 500 ms)
Default
(Range)
1.00
(0.00 - 10.00)