H6-05: Terminal RP Filter Time
No.
Name
(Hex.)
H6-05
Terminal RP Filter Time
(0430)
RUN
H6-06: Terminal MP Monitor Selection
No.
Name
(Hex.)
H6-06
Terminal MP Monitor
Selection
(0431)
RUN
Note:
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
• Use the pulse train monitor as the sourcing output.
Output Voltage
• Use the pulse train monitor as the sinking input
External Power Supply (V)
Sinking current (mA)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
Sets the time constant for the pulse train input primary delay filters.
V/f
CL-V/f
OLV
CLV
Sets a function for pulse train monitor output terminal MP. Sets the "x-xx" part of the Ux-xx monitor.
VRL(V)
5 V or more
8 V or more
10 V or more
Figure 2.115 Circuit Diagram When Used as the Sourcing Output
Figure 2.116 Circuit Diagram When Used as the Sinking Input
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Load Impedance (kΩ)
12 VDC ± 10%, 15 VDC ± 10%
2.8 H: Terminal Functions
Default
(Range)
0.10 s
(0.00 - 2.00 s)
Default
(Range)
102
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
855)
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more
16 mA or less
2
429