2.8 H: Terminal Functions
The Run command source or frequency reference source is an external source set with b1-01 [Frequency Reference
Selection 1], b1-15 [Frequency Reference Selection 2], b1-02 [Run Command Selection 1], or b1-16 [Run Command
Selection 2].
3D: During Speed Search
Setting Value
Function
3D
During Speed Search
Note:
Refer to "b3: Speed Search" for more information.
3E: PID Feedback Low
Setting Value
Function
3E
PID Feedback Low
The drive detects FbL [PID Feedback Loss] when the PID feedback value < b5-13 [PID Feedback Loss Detection
Lvl] for longer than the time set in b5-14 [PID Feedback Loss Detection Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
3F: PID Feedback High
Setting Value
Function
3F
PID Feedback High
The drive detects FbH [Excessive PID Feedback] when the PID feedback value > b5-36 [PID High Feedback
Detection Lvl] for longer than the time set in b5-37 [PID High Feedback Detection Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
4A: During KEB Ride-Thru
Setting Value
Function
4A
During KEB Ride-Thru
Note:
Refer to "KEB Ride-Thru function" for more information.
4B: During Short Circuit Braking
Setting Value
Function
4B
During Short Circuit Braking
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this function is available when you use a PM motor.
• Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
4C: During Fast Stop
Setting Value
Function
4C
During Fast Stop
402
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive is doing speed search.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects FbL [PID Feedback Loss].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects FbH [Excessive PID Feedback].
V/f
CL-V/f
OLV
CLV
AOLV
The activates during KEB Ride-Thru.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates during Short Circuit Braking.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the fast stop is in operation.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8002B GA800 Drive Programming