b8-20: E-Save Search Width
No.
Name
(Hex.)
b8-20
E-Save Search Width
(0B41)
Expert
An increase in the value can make the operational efficiency better. However, if the load inertia is small, it may be
necessary to adjust the value to prevent machine vibration.
Note:
• If low inertia causes vibration in the machine, decrease the setting value in 1.0-degree increments and check the response.
• To make the motor more efficient, increase the setting value in 1.0-degreee increments until the point immediately before machine vibration
starts to occur.
b8-21: PM E-Save Search Gain
No.
Name
(Hex.)
b8-21
PM E-Save Search Gain
(0B42)
Expert
When you decrease the value of C5-01 [ASR Proportional Gain 1], also decrease the value of b8-21 to keep the
correct ratio.
b8-22: PM E-Save Search LPF Cutoff Freq
No.
Name
(Hex.)
b8-22
PM E-Save Search LPF
Cutoff Freq
(0B43)
Expert
b8-23: PM E-Save Search Limit
No.
Name
(Hex.)
b8-23
PM E-Save Search Limit
(0B44)
Expert
When the motor characteristics are correct, increase this value to make the motor more efficient.
b8-24: PM E-Save High Freq ACR Gain
No.
Name
(Hex.)
b8-24
PM E-Save High Freq ACR
Gain
(0B45)
Expert
Note:
If the drive detects oC [Overcurrent], decrease the value.
b8-25: PM E-Save Search Start Level
No.
Name
(Hex.)
b8-25
PM E-Save Search Start
Level
(0B46)
Expert
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amplitude of Energy-saving control search operations.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of Energy-saving control search operations.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency of the filter used to extract the high-efficiency phase from search operations.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the search operations output limit. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for high-frequency current control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the start level for search operations.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.3 b: Application
Default
(Range)
1.0 degrees
(0.1 - 5.0 degrees)
Default
(Range)
0.3Hz
(0.1 - 20.0 Hz)
Default
(Range)
10.0 Hz
(1.0 - 30.0 Hz)
Default
(Range)
15.0 degrees
(0.0 - 30.0 degrees)
Default
(Range)
200.0 Hz
(100.0 - 1000.0 Hz)
Default
2
(Range)
10.0%
(0.0 - 100.0%)