2.7 F: Options
5 : PPO (bit0, Enter)
This function operates when bit 0 and bit 4 in the register STW have values of 1 (operate). Refer to the PROFIBUS-
DP communication manual for more information.
F6-35: CANopen Node ID Selection
No.
Name
(Hex.)
F6-35
CANopen Node ID Selection
(03D0)
Note:
Be sure to set an address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings will cause
AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
F6-36: CANopen Communication Speed
No.
Name
(Hex.)
F6-36
CANopen Communication
Speed
(03D1)
0 : Auto-detection
The drive detects the network communication speed and automatically adjusts the communications speed.
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
F6-45: BACnet Node Address
No.
Name
(Hex.)
F6-45
BACnet Node Address
(02FB)
F6-46: BACnet Baud Rate
No.
Name
(Hex.)
F6-46
BACnet Baud Rate
(02FC)
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
346
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CANopen communication. Restart the drive after you change the parameter
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the CANopen communications speed. Restart the drive after you change the parameter setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the BACnet communications speed.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0
(0 - 126)
Default
(Range)
6
(0 - 8)
Default
(Range)
1
(0 - 127)
Default
(Range)
3
(0 - 8)