• Output current is a minimum of 109% of the drive rated current, the drive is in Normal Duty mode, and the
frequency reference is 7 Hz or more.
• Output current is a minimum of 112% of the drive rated current, the drive is in Heavy Duty mode, and the
frequency reference is 7 Hz or more.
When the drive switches the carrier frequency to the set value, it uses the delay time set in L8-40 [CarrierFreqReduct
Off DelayTime] and a hysteresis of 12%.
L8-40: Carrier Freq Reduction Off-Delay
No.
Name
(Hex.)
L8-40
Carrier Freq Reduction Off-
Delay
(04F1)
Set L8-40 ≠ 0.00 to enable the carrier frequency reduction function during start-up. When operation starts, the drive
automatically decreases the carrier frequency. When the time set in L8-40 is expired, the carrier frequency returns to
the value set in C6-02 [Carrier Frequency Selection].
When L8-38 = 1, 2 [Carrier Frequency Reduction = Enabled], the drive applies L8-40 as the time for the carrier
frequency to return to its configured value after it is decreased.
L8-41: High Current Alarm Selection
No.
Name
(Hex.)
L8-41
High Current Alarm
Selection
(04F2)
0 : Disabled
The drive will not detect HCA [Current Alarm].
1 : Enabled
If the output current is more than 150% of the drive rated current, the drive will detect HCA.
The MFDO terminal set for an alarm [H2-01 to H2-03 = 10] activates.
L8-51: STPo I Detection Level
No.
Name
(Hex.)
L8-51
STPo I Detection Level
(0471)
Expert
Note:
The detection level is automatically calculated when L8-51 = 0.
L8-52: STPo Integration Level
No.
Name
(Hex.)
L8-52
STPo Integration Level
(0472)
Expert
L8-53: STPo Integration Time
No.
Name
(Hex.)
L8-53
STPo Integration Time
(0473)
Expert
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to cause an HCA [Current Alarm] when the output current is more than 150% of the
drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the STPo [Motor Step-Out Detected] detection level as a percentage of the motor rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Motor Step-Out Detected] related to the ACR integral value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the drive detects STPo after it is more than the value of L8-51 [STPo I
Detection Level].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.9 L: Protection Functions
Default
(Range)
Determined by A1-02
(0.00 - 2.00 s)
Default
(Range)
0
(0, 1)
Default
(Range)
0.0%
(0.0 - 300.0%)
Default
(Range)
1.0
(0.1 - 2.0)
Default
(Range)
1.0 s
(1.0 - 10.0 s)
2
481