YASKAWA GA800 Programming Manual page 244

Ac drive for industrial applications
Table of Contents

Advertisement

2.3 b: Application
Note:
If there is vibration in the machine, increase the value.
b8-26: PM E-Save Power Setpoint
No.
Name
(Hex.)
b8-26
PM E-Save Power Setpoint
(0B47)
Expert
b8-28: Over Excitation Action Selection
No.
Name
(Hex.)
b8-28
Over Excitation Action
Selection
(0B8B)
Expert
When operation is not stable at low speeds, set this parameter to 1 to enable the function.
0 : Disabled
1 : Enabled
b8-29: Energy Saving Priority Selection
No.
Name
(Hex.)
b8-29
Energy Saving Priority
Selection
(0B8C)
Enable this parameter when there are small changes in the load. It is possible that the motor cannot respond correctly
to changes in the load.
0 : Priority: Drive Response
1 : Priority: Energy Savings
b8-50: Standby Mode Selection
No.
Name
(Hex.)
b8-50
Standby Mode Selection
(0B0D)
0 : Disabled
1 : Enabled
Standby Mode decreases how much power the drive consumes when it is in standby.
Standby Mode waits for the drive to stop, uses the relay output of an MFDO terminal to shut off the input side
electromagnetic contactor (MC), then shuts off the main circuit power supply.
Note:
These conditions are also necessary for Standby Mode:
• Connect an external 24 V power supply.
• Connect an electromagnetic contactor to the drive input side and connect the MFDO terminal set for H2-xx = 65 [Standby Output]. When
the MFDO terminal is OFF, the electromagnetic contactor must be OFF.
• Frequently starting and stopping the drive and regularly opening and closing the electromagnetic contactor will decrease the service life of
the drive.
244
V/f
CL-V/f
OLV
CLV
AOLV
Sets a value to increase torque accuracy.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for excitation operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the priority of drive response between changes to the load or Energy-saving control. Enable this
to prioritize energy-saving control. Disable this to prioritize tracking related to fast load changes, and
prevent motor stall.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Standby Mode function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0.0%
(-10.0 - +10.0%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)