Note:
When you set this function, it will disable the setting value of b2-02 [DC Injection Braking Current].
7: Torque Detection Level
Setting Value
Function
7
Torque Detection Level
When A1-02 = 0, 1, 5 [Control Method Selection = V/f, CL-V/f, OLV/PM], the drive rated current is 100%. When A1-
02 = 2, 3, 4, 6, 7, 8 [OLV, CLV, AOLV, AOLV/PM, CLV/PM, EZOLV], the motor rated torque is 100%.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02 [Torque Detection Level 1].
8: Stall Prevent Level During Run
Setting Value
Function
8
Stall Prevent Level During
Run
Note:
The Stall Prevent Level During Run is based on the smaller of these two values:
• Analog input value of MFAI terminal
• L3-06 [Stall Prevent Level during Run]
9: Output Frequency Lower Limit
Setting Value
Function
9
Output Frequency Lower
Limit
B: PID Feedback
Setting Value
Function
B
PID Feedback
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Figure 2.106 DC Injection Braking Current through Analog Input
V/f
CL-V/f
OLV
CLV
Enters a signal to adjust the overtorque/undertorque detection level.
V/f
CL-V/f
OLV
CLV
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Figure 2.107 Stall Prevention Level during Run with Analog Input
V/f
CL-V/f
OLV
CLV
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
V/f
CL-V/f
OLV
CLV
Enter the PID feedback value as a percentage of the maximum output frequency.
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.8 H: Terminal Functions
415