YASKAWA GA800 Programming Manual page 209

Ac drive for industrial applications
Table of Contents

Advertisement

This function stops then restarts a coasting motor and increases motor flux to make high starting torque (a process
called initial excitation). Set this parameter to 0.00 to disable the function.
Note:
• To restart a coasting motor, use DC Injection Braking to stop and then restart the motor, or enable Speed Search. Enable DC Injection
Braking or Speed Search to prevent ov [Overvoltage] and oC [Overcurrent] faults.
• Sets the time of Initial Excitation at start when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With Encoder].
b2-04: DC Inject Braking Time at Stop
No.
Name
(Hex.)
b2-04
DC Inject Braking Time at
Stop
(018C)
This function fully stops a motor with a large inertia during deceleration and will not let the inertia continue to rotate
the motor.
Set this parameter to 0.00 to disable the function.
When a longer time is required to stop the motor, increase the value.
Note:
Sets the time of Zero Speed Control at stop when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With Encoder].
b2-08: Magnetic Flux Compensation Value
No.
Name
(Hex.)
b2-08
Magnetic Flux
Compensation Value
(0190)
This parameter is effective when you start a high-capacity motor (a motor with a large secondary circuit time
constant). This function can quickly increase motor flux to make high starting torque (a process called initial
excitation).
The current level for DC Injection Braking at start changes linearly from the setting of b2-08 to the setting of b2-03 as
shown in
Figure
2.27.
Note:
• If b2-08 < 100%, flux will develop very slowly.
• When b2-08 = 0%, the DC current level will be the DC Injection current set in b2-02 [DC Injection Braking Current].
• If b2-08 is set too high, DC Injection Braking at start can cause a large noise. Adjust b2-08 to decrease the volume to the permitted level.
b2-12: Short Circuit Brake Time @ Start
No.
Name
(Hex.)
b2-12
Short Circuit Brake Time @
Start
(01BA)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
Sets the DC Injection Braking Time at stop. Sets the time of Zero Speed Control at stop when A1-02
= 3, 7 [Control Method Selection = CLV, CLV/PM].
V/f
CL-V/f
OLV
CLV
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial Excitation)
as a percentage of E2-03 [Motor No-Load Current].
Figure 2.27 DC Current Level during DC Injection Braking at Start
V/f
CL-V/f
OLV
CLV
Sets the Short Circuit Braking time at start.
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.3 b: Application
Default
(Range)
Determined by A1-02
(0.00 - 10.00 s)
Default
(Range)
0%
(0 - 1000%)
2
Default
(Range)
0.00 s
(0.00 - 25.50 s)