YASKAWA GA800 Programming Manual page 28

Ac drive for industrial applications
Table of Contents

Advertisement

1.5 b: Application
No.
Name
(Hex.)
b5-11
PID Output Reverse
Selection
(01AF)
b5-12
Feedback Loss Detection
Select
(01B0)
b5-13
PID Feedback Loss
Detection Lvl
(01B1)
b5-14
PID Feedback Loss
Detection Time
(01B2)
b5-15
PID Sleep Function Start
Level
(01B3)
b5-16
PID Sleep Delay Time
(01B4)
b5-17
PID Accel/Decel Time
(01B5)
RUN
b5-18
b5-19 PID Setpoint
Selection
(01DC)
b5-19
PID Setpoint Value
(01DD)
RUN
b5-20
PID Unit Selection
(01E2)
b5-34
PID Output Lower Limit
Level
(019F)
RUN
b5-35
PID Input Limit Level
(01A0)
RUN
28
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables reverse motor rotation for negative PID control
output.
0 : Lower Limit is Zero
1 : Negative Output Accepted
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive response to PID Feedback Low/High. Sets drive operation after the drive
detects PID feedback Low/High.
0 : Digital Out Only, Always Detect
1 : Alarm + Digital Out, Always Det
2 : Fault + Digital Out, Always Det
3 : Digital Out Only, @ PID Enable
4 : Alarm + Digital Out, @PID Enable
5 : Fault + Digital Out, @PID Enable
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level that triggers PID Feedback Loss [FbL] detection as a percentage of the
Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that PID Feedback must be less than b5-13 [PID Feedback Loss
Detection Lvl] to detect PID Feedback Loss [FbL].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output level that triggers the PID Sleep function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a delay time to start or stop the PID Sleep function.
V/f
CL-V/f
OLV
CLV
AOLV
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the
drive. This is a soft-starter for the PID setpoint.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables b5-19 [PID Setpoint Value].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID setpoint when b5-18 = 1 [b5-19 PID Setpoint Selection = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of digits to set and show the PID setpoint.
0 : 0.01Hz units
1 : 0.01% units
2 : rev/min
3 : User Units
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output lower limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output upper limit for the PID control as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
0
230
(0, 1)
0
230
(0 - 5)
0%
231
(0 - 100%)
1.0 s
231
(0.0 - 25.5 s)
Determined by A1-02
231
(0.0 - 590.0)
0.0 s
231
(0.0 - 25.5 s)
0.0 s
231
(0.0 - 6000.0 s)
0
232
(0, 1)
0.00%
232
(0.00 - 100.00%)
1
232
(0 - 3)
0.0%
232
(-100.0 - +100.0%)
1000.0%
233
(0.0 - 1000.0%)

Advertisement