Note:
• When you use this method to set the torque limit, it enables the lower torque limit:
–Set H3-02, H3-06, or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-02: Reverse Torque Limit
No.
Name
(Hex.)
L7-02
Reverse Torque Limit
(04A8)
RUN
Note:
• When you use this method to set the torque limit, it enables the lower torque limit:
–Set H3-02, H3-06, or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-03: Forward Regenerative Trq Limit
No.
Name
(Hex.)
L7-03
Forward Regenerative Trq
Limit
(04A9)
RUN
Note:
• When you use this method to set the torque limit, it enables the lower torque limit:
–Set H3-02, H3-06, or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-04: Reverse Regenerative Trq Limit
No.
Name
(Hex.)
L7-04
Reverse Regenerative Trq
Limit
(04AA)
RUN
Note:
• When you use this method to set the torque limit, it enables the lower torque limit:
–Set H3-02, H3-06, or H3-10 = 10, 15 [MFAI Function Select = Forward, Reverse/Regenerative Torque Limit].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-06: Torque Limit Integral Time
No.
Name
(Hex.)
L7-06
Torque Limit Integral Time
(04AC)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the
100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time constant for the torque limit function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.9 L: Protection Functions
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200 ms
(5 - 10000 ms)
2
473