2.4 C: Tuning
If C5-12 = 1 or C5-32 = 1 [Enabled] in Closed Loop V/f
Control, over/undershoot occurs when you change speeds.
Oscillation at low speed and response is too slow at high
speed.
Oscillation at high speed and response is too slow at low
speed.
■
C5-01: ASR Proportional Gain 1
No.
Name
(Hex.)
C5-01
ASR Proportional Gain 1
(021B)
RUN
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will
cause vibration.
Note:
• The drive usually sets Motor 1 ASR with C5-01 and C5-02 [ASR Integral Time 1]. You can switch between C5-01 and C5-03 [ASR
Proportional Gain 2] by setting H1-xx = 77 [MFDI Function Selection = ASR Gain (C5-03) Select]. You can also use C5-01 and C5-02 as
alternatives to C5-03 and C5-04, respectively, when the speed is less than or equal to the frequency set in C5-07 [ASR Gain Switchover
Frequency].
• The drive automatically adjusts C5-01 in ASR Tuning.
■
C5-02: ASR Integral Time 1
No.
Name
(Hex.)
C5-02
ASR Integral Time 1
(021C)
RUN
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
■
C5-03: ASR Proportional Gain 2
No.
Name
(Hex.)
C5-03
ASR Proportional Gain 2
(021D)
RUN
A higher gain provides a higher speed response. Usually, the gain increases with larger loads. Too much gain will
cause vibration.
■
C5-04: ASR Integral Time 2
No.
Name
(Hex.)
C5-04
ASR Integral Time 2
(021E)
RUN
When you increase the integral time, the responsiveness will decrease. An integral time that is too short can cause
oscillation.
264
Problem
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to adjust ASR response.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ASR integral time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to adjust ASR response.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ASR integral time.
• Decrease C5-01/C5-03.
• Increase C5-02/C5-04.
-
• Decrease the value set to C5-05.
• Closed Loop V/f Control Mode:
Use C5-03 and C5-04 at maximum speed and C5-01 and
C5-02 at minimum speed to set different ASR settings.
• Closed Loop Vector Control, PM Advanced Open Loop
-
Vector Control, and PM Closed Loop Vector Control:
Use C5-01 to C5-04 to set the best ASR settings for high
and low speed. Use C5-07 [ASR Gain Switchover
Frequency] to switch the ASR proportional gain and
ASR integral time as specified by the output frequency.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Possible Solutions
Default
(Range)
Determined by A1-02
(0.00 - 300.00)
Default
(Range)
Determined by A1-02
(0.000 - 60.000 s)
Default
(Range)
Determined by A1-02
(0.00 - 300.00)
Default
(Range)
Determined by A1-02
(0.000 - 60.000 s)