• L3-11 = 1 [OV Suppression Function Select = Enabled]
• H1-xx = 7A or 7B [MFDI Function Select = KEB Ride-Thru 2 (N.O./N.C.)]
Note:
• If stall prevention during deceleration function causes large speed or current ripples and L2-29 = 1, H1-xx = 7A or 7B, or L3-04 = 2,
gradually decrease this parameter in 0.05-unit increments. If the drive detects ov [Overvoltage] or oC [Overcurrent], decrease this
parameter. If you decrease the gain too much, it can cause a delay in control in the DC bus voltage or the deceleration time could be longer
than the best deceleration time.
• If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If there
are large speed ripples, gradually decrease this parameter in 0.05-unit increments.
L3-22: PM Stall Prevention Decel Time
No.
Name
(Hex.)
L3-22
PM Stall Prevention Decel
Time
(04F9)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at the
time when a motor stall occurs.
L3-23: Stall P Reduction at Constant HP
No.
Name
(Hex.)
L3-23
Stall P Reduction at
Constant HP
(04FD)
0 : Use L3-06 for Entire Speed Range
The drive uses the level set in L3-06 [Stall Prevent Level during Run] through the full speed range.
1 : Automatic Reduction @ CHP Region
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of the
L3-06 value.
L3-24: Motor Accel Time @ Rated Torque
No.
Name
(Hex.)
L3-24
Motor Accel Time @ Rated
Torque
(046E)
Expert
Set one of these parameters to enable L3-20:
• L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
• L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
• L3-11 = 1 [Overvoltage Suppression Select = Enabled]
• H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
When Auto-Tuning changes the value of E2-11 [Motor Rated Power], the drive will automatically set L3-24 to the value for a Yaskawa
standard motor (4 poles). When you use a PM motor, the drive uses the value in E5-01 [PM Motor Code Selection] to change L3-24.
Automatically Adjust Parameters
When A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM], do Inertia Tuning. Parameters are automatically
adjusted.
Manually Adjust Parameters
Use this formula to find the motor acceleration time:
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM motor
and detected motor stalls. This function is applicable when L3-01 = 1 [Stall Prevent Select
duringAccel = General Purpose].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to automatically decrease the Stall Prevention Level during Run for constant output
ranges.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.9 L: Protection Functions
Default
(Range)
0.0 s
(0.0 - 6000.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
Determined by o2-04, C6-
01, E2-11, and E5-01
(0.001 - 10.000 s)
2
459