YASKAWA GA800 Programming Manual page 423

Ac drive for industrial applications
Table of Contents

Advertisement

H5-02: Communication Speed Selection
No.
Name
(Hex.)
H5-02
Communication Speed
Selection
(0426)
Note:
Restart the drive after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
H5-03: Communication Parity Selection
No.
Name
(Hex.)
H5-03
Communication Parity
Selection
(0427)
Note:
Restart the drive after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
H5-04: Communication Error Stop Method
No.
Name
(Hex.)
H5-04
Communication Error Stop
Method
(0428)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows CE and the drive continues operation. The output terminal set for Alarm [H2-01 to H2-03 = 10]
activates.
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communications speed for MEMOBUS/Modbus communications.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communications parity used for MEMOBUS/Modbus communications.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor Stopping Method when the drive detects CE [Modbus Communication Error] issues.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.8 H: Terminal Functions
Default
(Range)
3
(0 - 8)
Default
(Range)
0
(0 - 2)
Default
(Range)
3
(0 - 3)
423
2