2.4 C: Tuning
C3-16: Vout Modulation Limit Start Lvl
No.
Name
(Hex.)
C3-16
Vout Modulation Limit Start
Lvl
(0261)
Expert
C3-17: Vout Modulation Limit Max Level
No.
Name
(Hex.)
C3-17
Vout Modulation Limit Max
Level
(0262)
Expert
C3-18: Output Voltage Limit Level
No.
Name
(Hex.)
C3-18
Output Voltage Limit Level
(0263)
Expert
C3-21: Motor 2 Slip Compensation Gain
No.
Name
(Hex.)
C3-21
Motor 2 Slip Compensation
Gain
(033E)
RUN
Note:
Correctly set these parameters before changing the slip compensation gain:
• E4-01 [Motor 2 Rated Current]
• E4-02 [Motor 2 Rated Slip]
• E4-03 [Motor 2 Rated No-Load Current]
Use these settings to adjust this parameter as necessary:
• If the motor speed is slower than the frequency reference, increase C3-01 in 0.1 unit increments.
• If the motor speed is higher than the frequency reference, decrease the setting of this parameter in 0.1-unit
increments.
C3-22: Motor 2 Slip Comp Delay Time
No.
Name
(Hex.)
C3-22
Motor 2 Slip Comp Delay
Time
(0241)
RUN
Use these settings to adjust this parameter as necessary:
• When the speed is not stable, increase the setting.
• When the slip compensation response is too slow, decrease the setting.
C3-23: Motor 2 Slip Compensation Limit
No.
Name
(Hex.)
C3-23
Motor 2 Slip Compensation
Limit
(0242)
256
V/f
CL-V/f
OLV
CLV
AOLV
Sets the modulation factor that starts the output voltage limit operation when C3-05 = 1 [Output
Voltage Limit Selection = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the modulation factor used with C3-18 [Output Voltage Limit Level] for the output voltage limit
operation when C3-05 = 1 [Output Voltage Limit Selection = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum drop width of the voltage reference when C3-05 = 1 [Output Voltage Limit
Selection = Enabled].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the slip compensation delay time for motor 2 when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit for the slip compensation function as a percentage of the motor 2 rated slip.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
90.0%
(70.0 - 90.0%)
Default
(Range)
100.0%
(85.0 - 100.0%)
Default
(Range)
90.0%
(50.0 - 100.0%)
Default
(Range)
Determined by E3-01
(0.0 - 2.5)
Default
(Range)
Determined by E3-01
(0 - 10000 ms)
Default
(Range)
200%
(0 - 250%)