YASKAWA GA800 Programming Manual page 203

Ac drive for industrial applications
Table of Contents

Advertisement

1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
b1-09: LOCAL/REMOTE Select during RUN
No.
Name
(Hex.)
b1-09
LOCAL/REMOTE Select
during RUN
(0188)
Expert
0 : Disabled
1 : Enabled
When you switch the operation mode from REMOTE to LOCAL during run, the drive writes this REMOTE operation
status to the keypad:
• Frequency reference during run
• RUN/STOP status of the keypad
• FWD/REV
• JOG
Note:
When b1-09 = 1, the drive will detect oPE05 [Run Cmd/Freq Ref Source Sel Err] if you set one of these parameter values:
• b1-02 = 0 [Run Command Selection 1 = Keypad]
• b1-16 = 0 [Run Command Selection 2 = Keypad] and H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
• H1-xx = 3 to 6, 12, 13, 32 [Multi-Step Speed Reference 1 to 4, Jog Reference Selection, Forward Jog, Reverse Jog]
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
0 : Standard
1 : Switch Phase Order
b1-15: Frequency Reference Selection 2
No.
Name
(Hex.)
b1-15
Frequency Reference
Selection 2
(01C4)
This parameter is enabled when H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection] is
activated.
Note:
• Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• If the frequency reference is 0 Hz or ≤ E1-09 [Minimum Output Frequency] and the drive receives a Run command, the
will flash. Check the setting for the frequency reference input and enter a value more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that lets you use the
REMOTE Modes.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for frequency reference 2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
during operation to switch between LOCAL and
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.3 b: Application
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)
on the keypad
2
203