YASKAWA GA800 Programming Manual page 395

Ac drive for industrial applications
Table of Contents

Advertisement

E: Fault
Setting Value
Function
E
Fault
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting Value
Function
F
Not Used
10: Alarm
Setting Value
Function
10
Alarm
11: Fault Reset Command Active
Setting Value
Function
11
Fault Reset Command
Active
12: Timer Output
Setting Value
Function
12
Timer Output
Note:
Refer to "b4: Timer Function" for more information.
13: Speed Agree 2
Setting Value
Function
13
Speed Agree 2
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if signals from the PLC are not configured.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive detects a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting when the drive uses the timer function as an output terminal.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width
(+/-)].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
2.8 H: Terminal Functions