YASKAWA GA800 Programming Manual page 314

Ac drive for industrial applications
Table of Contents

Advertisement

2.6 E: Motor Parameters
E9-02: Maximum Speed
No.
Name
(Hex.)
E9-02
Maximum Speed
(11E5)
Note:
The unit of measure changes when the setting of o1-04 [V/f Pattern Display Unit].
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
E9-03: Rated Speed
No.
Name
(Hex.)
E9-03
Rated Speed
(11E6)
EZ Tuning automatically sets this parameter to the value of [Rated Speed].
Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
E9-04: Base Frequency
No.
Name
(Hex.)
E9-04
Base Frequency
(11E7)
Note:
The unit of measure changes when the setting of o1-04 [V/f Pattern Display Unit].
EZ Tuning automatically sets this parameter to the value of [Base Frequency].
E9-05: Base Voltage
No.
Name
(Hex.)
E9-05
Base Voltage
(11E8)
EZ Tuning automatically sets this parameter to the value of [Base Voltage].
E9-06: Motor Rated Current (FLA)
No.
Name
(Hex.)
E9-06
Motor Rated Current (FLA)
(11E9)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: models 2004 to 2042, 4002 to 4023
• 0.1 A: models 2056 to 2415, 4031 to 4720
The value set for E9-06 becomes the reference value for motor protection. Enter the motor rated current shown on the
motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for "Motor Rated Current".
314
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum speed of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated rotation speed of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated frequency of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated current in amps.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
Determined by E9-01
(40.0 - 120.0 Hz)
Default
(Range)
Determined by E9-01
-1
(100 - 7200 min
)
Default
(Range)
Determined by E9-01
(40.0 - 120.0 Hz)
Default
(Range)
200 V Class: 230.0 V, 400 V:
460.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
Default
(Range)
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)

Advertisement

Table of Contents
loading

Table of Contents