H: Terminal Functions

H parameters are used to assign functions to external input and output terminals.

H1: Digital Inputs

H1 Parameters set the MFDI terminal functions.
H1-01 to H1-08 Terminal S1 to S8 Function Selection
The drive has 8 MFDI terminals. Refer to
No.
H1-01
Terminal S1 Function Selection
H1-02
Terminal S2 Function Selection
H1-03
Terminal S3 Function Selection
H1-04
Terminal S4 Function Selection
H1-05
Terminal S5 Function Selection
H1-06
Terminal S6 Function Selection
H1-07
Terminal S7 Function Selection
H1-08
Terminal S8 Function Selection
*1
The value in parentheses identifies the default setting when you set A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization].
Refer to
Table 2.55
the and use H1-xx [MFDI Function Select] to set the function.
Setting Value
*1
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
*1
8
Baseblock Command (N.O.)
*1
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
C
Analog Terminal Enable Selection
D
Ignore Speed Fdbk (V/f w/o Enc)
E
ASR Integral Reset
F
Not Used
10
Up Command
11
Down Command
*1
12
Forward Jog
*1
13
Reverse Jog
14
Fault Reset Procedure
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Table 2.54
Table 2.54 MFDI Default Settings and Functions
Name
Table 2.55 MFDI Setting Values
Function
Reference
361
362
362
362
363
363
363
363
363
364
364
364
364
364
364
365
365
366
367
367
368
for drive default settings and functions.
Default
*1
40 (F)
Forward RUN (2-Wire)
*1
41 (F)
Reverse RUN (2-Wire)
24
External Fault (NO-Always-Coast)
14
Fault Reset
*1
3 (0)
Multi-Step Speed Reference 1
*1
4 (3)
Multi-Step Speed Reference 2
*1
6 (4)
Jog Reference Selection
8
Baseblock Command (N.O.)
Setting Value
*1
15
Fast Stop (N.O.)
16
Motor 2 Selection
*1
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Programming Lockout
1E
Reference Sample Hold
*1
20 to 2F
External Fault
30
PID Integrator Reset
31
PID Integrator Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter Disable
35
PID Input (Error) Invert
3E
PID Setpoint Selection 1
3F
PID Setpoint Selection 2
*1
40
Forward RUN (2-Wire)
*1
41
Reverse RUN (2-Wire)
*1
42
Run Command (2-Wire Sequence 2)
*1
43
FWD/REV (2-Wire Sequence 2)
44
Add Offset Frequency 1 (d7-01)

2.8 H: Terminal Functions

Function
Function
Reference
368
368
369
369
370
370
370
370
371
371
372
372
372
372
372
372
373
373
373
374
374
2
357

Advertisement

Table of Contents
loading

Table of Contents