2.11 o: Keypad-Related Settings
o2-05: Home Mode Freq Ref Entry Mode
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
Name
(Hex.)
o2-06
Keypad Disconnect
Detection
(050A)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects oPr [Keypad Connection Fault], and the motor coasts to stop when the drive
detects a keypad disconnection.
o2-07: Keypad RUN Direction @ Power-up
No.
Name
(Hex.)
o2-07
Keypad RUN Direction @
Power-up
(0527)
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
0 : Forward
1 : Reverse
o2-09: Region Code
No.
Name
(Hex.)
o2-09
Reserved
(050D)
520
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that makes it necessary to push the
with the keypad when in Drive Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
-
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
to change the frequency reference value
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0
(0, 1)
and
on the
Default
(Range)
1
(0, 1)
Default
(Range)
0
(0, 1)