b5-05: Derivative Time (D)
No.
Name
(Hex.)
b5-05
Derivative Time (D)
(01A9)
RUN
When you increase the time setting, it will increase controller responsiveness, but it can also cause vibration. When
you decrease the time setting, it will suppress overshoot and decrease controller responsiveness.
Set b5-05 = 0.00 to disable D control.
b5-06: PID Output Limit
No.
Name
(Hex.)
b5-06
PID Output Limit
(01AA)
RUN
b5-07: PID Offset Adjustment
No.
Name
(Hex.)
b5-07
PID Offset Adjustment
(01AB)
RUN
b5-08: PID Primary Delay Time Constant
No.
Name
(Hex.)
b5-08
PID Primary Delay Time
Constant
(01AC)
RUN
Expert
Prevents resonance if there is a large quantity of mechanical friction or if rigidity is unsatisfactory. Set the value larger
than the resonant frequency cycle. A value that is too large will decrease drive responsiveness.
b5-09: PID Output Level Selection
No.
Name
(Hex.)
b5-09
PID Output Level Selection
(01AD)
Use this parameter in applications that decrease the drive output frequency when you increase the PID setpoint.
0 : Normal Output (Direct Acting)
A positive PID input increases the PID output (direct acting).
1 : Reverse Output (Reverse Acting)
A positive PID input decreases the PID output (reverse acting).
b5-10: PID Output Gain Setting
No.
Name
(Hex.)
b5-10
PID Output Gain Setting
(01AE)
RUN
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the derivative time (D) for PID control. This parameter adjusts system responsiveness.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum possible output from the PID controller as a percentage of the Maximum Output
Frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset for the PID control output as a percentage of the Maximum Output Frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PID control output. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the polarity of the PID output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount of gain to apply to the PID output.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.3 b: Application
Default
(Range)
0.00 s
(0.00 - 10.00 s)
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
0.0%
(-100.0 - +100.0%)
Default
(Range)
0.00 s
(0.00 - 10.00 s)
Default
(Range)
0
(0, 1)
Default
2
(Range)
1.00
(0.00 - 25.00)