YASKAWA GA800 Programming Manual page 392

Ac drive for industrial applications
Table of Contents

Advertisement

2.8 H: Terminal Functions
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ±
L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency
reference ± L4-02.
4: Frequency Detection 1
Setting Value
Function
4
Frequency Detection 1
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 + L4-
02.
OFF : The output frequency > L4-01 + L4-02.
392
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Figure 2.92 User-Defined Speed Agree 1 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the output frequency > L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection
Width]. After the terminal turns off, the terminal continues to remain off until the output frequency reaches the level set with L4-01.
Figure 2.93 Frequency Detection 1 Time Chart
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming